AC and DC breakdown tests were performed on large populations of oil-impregnated pressboard samples. The effect of voltage ramp rate on dielectric strength has been investigated. A statistical analysis of breakdown data was carried out using the Weibull distribution. The 90% confidence intervals of Weibull graphs were calculated. The study shows that dielectric strength and shape parameter change versus ramp rate. The variations are attributed to the size and number of defects. Discharges occur from the oil to the oil-pressboard interface and lead to breakdown. DC dielectric strength is larger than that corresponding to AC voltage. This is ascribed to the dissipated energy difference under the two types of field and the fatigue produced by the alternating voltage. This phenomenon is related to space charge. Under DC stress, dielectric strength is higher under negative polarity. It is assigned to the different quantities of space charge accumulated under the two polarities.

KEYWORDS

Oil-impregnated pressboard, dielectric strength, Weibull statistics